492 Fieldbus control through a fieldbus adapter
Automatically changed parameters (all adapters)
Specific fieldbus adapter parameters
Parameter
Setting (general) Setting (BCAN-11)
20.01 Ext1 commands
Fieldbus A
Embedded fieldbus
20.03 Ext1 in1
Not selected
Not selected
20.04 Ext1 in2
Not selected
Not selected
22.11 Ext1 speed ref1
FB A ref1
EFB ref1
22.22 Constant speed sel1
Not selected
Not selected
22.23 Constant speed sel2
Not selected
Not selected
23.11 Ramp set selection
Acc/Dec time 1
Acc/Dec time 1
28.11 Ext1 frequency ref1
FB A ref1
EFB ref1
28.22 Constant frequency sel1
Not selected
Not selected
28.23 Constant frequency sel2
Not selected
Not selected
28.71 Freq ramp set sel
Acc/Dec time 1
Acc/Dec time 1
31.11 Fault reset selection
DI1
DI2
50.01 FBA A enable
Enable
N/A
50.02 FBA A comm loss func
Fault
N/A
Parameter
Setting
CANopen (FCAN-01-M)
51.05 Profile
CiA 402
EtherCAT
51.02 Profile
CiA 402
PROFIBUS
51.02 Node address
3
51.05 Profile
ABB Drives
52.01 FBA A data in1
SW 16bit
52.02 FBA A data in2
Act1 16bit
53.01 FBA A data out1
CW 16bit
53.02 FBA A data out2
Ref1 16bit
PROFINET (default in FENA-21)
51.02 Protocol/profile
11 = PNIO ABB Pro (PROFINET IO protocol:
ABB Drives profile).
51.04 IP configuration
0 (Static IP)
52.01 Data In
4 (SW 16 bit (Status word (16 bit)))
52.02 Data In 2
5 (Act 1 16 bit)
53.01 Data Out 1
1 (CW 16 bit)
53.02 Data Out 2
2 (ref 1 16-bit)
Modbus TCP/IP
51.02 Protocol / Profile
1 = MB/TCP T16. (Modbus/TCP: ABB Drives
profile - Enhanced)
ACS380 FW.book Page 492 Friday, May 4, 2018 4:18 PM