116 Parameters
01.10
Motor torque
Motor torque in percent of the nominal motor torque. See
also parameter
01.30
Nominal torque scale
.
A filter time constant for this signal can be defined by
parameter
46.13
Filter time motor torque
.
-
-1600.0…1600.0%
Motor torque.
See par.
46.03
01.11
DC voltage
Measured intermediate circuit DC Link voltage.
-
0.00…2000.00 V
DC link voltage.
10 = 1 V
01.13
Output voltage
Calculated motor voltage in V AC.
-
0…2000 V
Motor voltage.
1 = 1 V
01.14
Output power
Measured output power in kW or hp, depending on setting
of parameter Power unit. The filter time constant can be
adjusted by parameter
46.14
Filter time power
.
-
-32768.00… 32767.00
kW or hp
Output power.
See par.
46.04
01.15
Output power % of
motor nom
Measured output power in % of nominal motor power.
-
-300.00… 300.00%
Output power.
10 = 1%
01.16
Output power % of
drive nom
Measured output power in % of drive nominal power. The
filter time constant can be adjusted by parameter
46.14
Filter time power
.
-
-300.00… 300.00%
Output power.
10 = 1%
01.17
Motor shaft power
Estimated mechanical power at motor shaft in kW or hp.
The unit is selected by parameter
96.16
Unit selection
.The
filter time constant can be adjusted by parameter
46.14
Filter time power
.
-
-32768.00… 32767.00
kW or hp
Motor shaft power.
See par.
46.04
01.18
Inverter GWh counter
Amount of energy that has passed through the drive (in
either direction) in full gigawatt-hours. The minimum value
is zero.
-
0…65535 GWh
Energy in GWh.
1 = 1 GWh
01.19
Inverter MWh counter
Amount of energy that has passed through the drive (in
either direction) in full megawatt-hours. Whenever the
counter rolls over,
01.18
Inverter GWh counter
is
incremented. The minimum value is zero.
-
0…1000 MWh
Energy in MWh.
1 = 1 MWh
01.20
Inverter kWh counter
Amount of energy that has passed through the drive (in
either direction) in full kilowatt-hours. Whenever the
counter rolls over,
01.19
Inverter MWh counter
is
incremented. The minimum value is zero.
-
0…1000 kWh
Energy in kWh.
10 = 1 kWh
01.24
Flux actual %
Used flux reference in percent of nominal flux of motor.
-
0…200%
Flux reference.
1 = 1%
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 116 Friday, May 4, 2018 4:18 PM