![ABB ACS380 Series Скачать руководство пользователя страница 115](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560115.webp)
Parameters 115
Parameter listing
No.
Name/Value
Description
Default
FbEq 16
01
01 Actual values
Basic signals for monitoring the drive.
All parameters in this group are read-only unless
otherwise noted.
Note:
Values of these actual signals are filtered with the
filter time defined in group
46 Monitoring/scaling settings
.
The selection lists for parameters in other groups mean
the raw value of the actual signal instead. For example, if
a selection is “Output frequency” it does not point to the
value of parameter
01.06
Output frequency
but to the raw
value.
01.01
Motor speed used
Measured or Estimated motor speed depending on the
type of feedback used in parameter
96.01
Motor feedback
selection
. A filter time constant for this signal can be
defined by parameter
46.11
Filter time motor speed
.
-
-30000.00… 30000.00
rpm
Measured or estimated motor speed.
See par.
46.01
01.02
Motor speed
estimated
Estimated motor speed in rpm. A filter time constant for
this signal can be defined by parameter
46.11
Filter time
motor speed
.
-
-30000.00… 30000.00
rpm
Estimated motor speed.
See par.
46.01
01.03
Motor speed %
Actual speed in percent of the motor synchronous speed.
The filter time constant can be adjusted by parameter
46.11
Filter time motor speed
.
-
-1000.00… 1000.00%
Motor speed.
See par.
46.01
01.04
Encoder 1 speed
filtered
Measured motor speed from Encoder 1. The filter time
constant can be adjusted by parameter
46.11
Filter time
motor speed
.
-
-30000 … 30000
1=1
01.06
Output frequency
Estimated drive output frequency in Hz. A filter time
constant for this signal can be defined by parameter
46.12
Filter time output frequency
.
-
-500.00…500.00 Hz
Estimated output frequency.
See par.
46.02
01.07
Motor current
Measured (absolute) motor current in A.
-
0.00…30000.00
Motor current.
See par.
46.05
01.08
Motor current % of
motor nom
Motor current (drive output current) in percent of the
nominal motor current.
-
0.0…1000.0%
Motor current.
1=1%
01.09
Motor current % of
drive nom
Motor current (drive output current) in percent of the
nominal drive current.
-
0.0…1000.0%
Motor current.
1=1%
ACS380 FW.book Page 115 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |