Parameters 135
10.25
RO1 ON delay
Defines the activation delay for relay output RO1.
0.0 -
t
On
=
10.25
RO1 ON delay
t
Off
=
10.26
RO1 OFF delay
0.0 … 3000.0 s
Activation delay for RO1.
10 = 1 -
10.26
RO1 OFF delay
Defines the deactivation delay for relay output RO1. See
parameter
10.25
RO1 ON delay
.
0.0 -
0.0 … 3000.0 s
Deactivation delay for RO1.
10 = 1 -
10.99
RO/DIO control word
Storage parameter for controlling the relay outputs eg.
through the embedded fieldbus interface. To control the
relay outputs (RO) of the drive, send a control word with
the bit assignments shown below as Modbus I/O data. Set
the target selection parameter of that particular data
(
58.101
…
58.114
) to
RO/DIO control word
. In the source
selection parameter of the desired output, select the
appropriate bit of this word.
0000h
0000h…FFFFh
RO control word.
1 = 1
10.101 RO1 toggle counter
Displays the number of times relay output RO1 has
changed states.
-
0…4294967000
State change count.
1 = 1
11
11 Standard DIO, FI, FO
Configuration of the digital inputs/outputs (DIO) for use as
digital inputs,
11.02
DIO delayed status
Displays the delayed status of digital input/outputs DIO2
and DIO1. This word is updated only after
activation/deactivation delays (if any are specified).
Example:
0010 = DIO2 is on, DIO1 is off.
This parameter is read-only.
-
0000b…0011b
Status of digital input/outputs.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
Bit
Name
Description
0
RO1
Source bits for relay outputs RO1…RO3 (see parameter
10.24
).
1
RO2
2
RO3
3
RO4
4
RO5
5…7
RO6-8
8...15
DIO1-8