![ABB ACS380 Series Скачать руководство пользователя страница 357](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560357.webp)
Additional parameter data 357
Parameter groups 1…9
No.
Name
Type
Range
Unit
FbEq32
01 Actual values
01.01 Motor speed used
Real
-30000.00…30000.00
rpm
100 = 1 rpm
01.02 Motor speed estimated
Real
-30000.00…30000.00
rpm
100 = 1 rpm
01.03 Motor speed %
Real
-1000.00…1000.00
%
100 = 1%
01.04 Encoder 1 speed filtered
Real
-30000 … 30000
rpm
100 = 1
01.06 Output frequency
Real
-500.00…500.00
Hz
100 = 1 Hz
01.07 Motor current
Real
0.00…30000.00
A
100 = 1 A
01.08 Motor current % of motor nom
Real
0.0…1000.0
%
10 = 1%
01.09 Motor current % of drive nom
Real
0.0…1000.0
%
10 = 1%
01.10 Motor torque
Real
-1600.0…1600.0
%
10 = 1%
01.11 DC voltage
Real
0.00…2000.00
V
100 = 1 V
01.13 Output voltage
Real
0…2000
V
1 = 1 V
01.14 Output power
Real
-32768.00…32767.00
kW or hp
100 = 1 unit
01.15 Output power % of motor nom
Real
-300.00…300.00
%
100 = 1%
01.16 Output power % of drive nom
Real
-300.00…300.00
%
100 = 1%
01.17 Motor shaft power
Real
-32768.00…32767.00
kW or hp
100 = 1 unit
01.18 Inverter GWh counter
Real
0…65535
GWh
1 = 1 GWh
01.19 Inverter MWh counter
Real
0…1000
MWh
1 = 1 MWh
01.20 Inverter kWh counter
Real
0…1000
kWh
1 = 1 kWh
01.24 Flux actual %
Real
0…200
%
1 = 1%
01.30 Nominal torque scale
Real
0.000…4000000
N·m or
lb·ft
1000 = 1 unit
01.50 Current hour kWh
Real
-21474836.48…
21474836.47
kWh
100 = 1 kWh
01.51 Previous hour kWh
Real
-21474836.48…
21474836.47
kWh
100 = 1 kWh
01.52 Current day kWh
Real
-21474836.48…
21474836.47
kWh
100 = 1 kWh
01.53 Previous day kWh
Real
-21474836.48…
21474836.47
kWh
100 = 1 kWh
01.54 Cumulative inverter energy
Real
-200000000.0…
200000000.0
kWh
1 = 1 kWh
01.55 Inverter GWh counter
(resettable)
Real
0…65535
GWh
1 = 1 GWh
01.56 Inverter MWh counter
(resettable)
Real
0…1000
MWh
1 = 1 MWh
01.57 Inverter kWh counter
(resettable)
Real
0…1000
kWh
1 = 1 kWh
01.58 Cumulative inverter energy
(resettable)
Real
-200000000.0…
200000000.0
kWh
1 = 1 kWh
01.61 Abs motor speed used
Real
0.00… 30000.00
rpm
100 = 1 rpm
01.62 Abs motor speed %
Real
0.00… 100.00%
%
100 = 1%
01.63 Abs output frequency
Real
0.00…500.00 Hz
Hz
100 = 1 Hz
ACS380 FW.book Page 357 Friday, May 4, 2018 4:18 PM