118 Parameters
01.57
Inverter kWh counter
(resettable)
Amount of energy that has passed through the drive (in
either direction) in full kilowatt-hours. Whenever the
counter rolls over,
01.56
Inverter MWh counter
(resettable)
is incremented. The minimum value is zero.
You can reset the value by setting it to zero. Resetting any
of parameters
01.55
…
01.58
resets all of them.
-
0…1000 kWh
Energy in kWh.
10 = 1 kWh
01.58
Cumulative inverter
energy (resettable)
Amount of energy that has passed through the drive (in
either direction) in full kilowatt-hours. The minimum value
is zero.
You can reset the value by setting it to zero. Resetting any
of parameters
01.55
…
01.58
resets all of them.
-
-200000000.0…
200000000.0 kWh
Energy in kWh.
10 = 1 kWh
01.61
Abs motor speed used
Absolute value of the motor speed used
01.01
Motor
speed used
.
-
0.00… 30000.00 rpm
1 = 1 rpm
01.62
Abs motor speed %
Absolute value of the motor speed %
01.03
Motor speed
%
-
0.00… 1000.00%
10 = 1%
01.63
Abs output frequency
Absolute value of the output frequency
01.06 Output
frequency
-
0.00…500.00 Hz
1 = 1 Hz
01.64
Abs motor torque
Absolute value of the motor torque
01.10
Motor torque
.
-
0.0...1600.0%
1 = 1%
01.65
Abs output power
Absolute value of the output power
01.14
Output power
.
-
0.00...32767.00 kW
1 = 1 kW
01.66
Abs output power %
mot nom
Absolute value of the output power % of motor nominal
01.15
Output power % of motor nom
.
-
0.00… 300.00%
1 = 1%
01.67
Abs output power %
drive nom
Absolute value of the output power % of drive nominal
01.16
Output power % of drive nom
.
-
0.00… 300.00%
1= 1%
01.68
Abs motor shaft power
Absolute value of the motor shaft power
01.17
Motor shaft
power
.
-
0.00...332767.00 kW
1 = 1 kW
03
03 Input references
Values of references received from various sources.
All parameters in this group are read-only unless
otherwise noted.
03.01
Panel reference
Local mode reference is given from the control panel.
0
-100000.00…
100000.00 rpm, Hz or
%
Control panel or PC tool reference.
1 = 10 unit
03.02
Panel reference
remote
Remote mode reference given from the control panel.
-
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 118 Friday, May 4, 2018 4:18 PM