192 Parameters
23.23
Emergency stop time
Defines the time inside which the drive is stopped if an
emergency stop Off3 is activated (ie. the time required for
the speed to change from the speed value defined by
parameter
46.01
Speed scaling
or
46.02
Frequency
scaling
to zero). Emergency stop mode and activation
source are selected by parameters
21.04
Emergency stop
mode
and
21.05
Emergency stop source
respectively.
Emergency stop can also be activated through fieldbus.
Note:
• Emergency stop Off1 uses the standard deceleration
ramp as defined by parameters
23.11
…
23.15
.
• The same parameter value is also used in frequency
control mode (ramp parameters
28.71
…
28.75
).
3.000 s
0.000 …1800.000 s
Emergency stop Off3 deceleration time.
10 = 1 s
23.28
Variable slope enable
Activates the variable slope function, which controls the
slope of the speed ramp during a speed reference
change. This allows for a constantly variable ramp rate to
be generated, instead of just the standard two ramps
normally available.
If the update interval of the signal from an external control
system and the variable slope rate (
23.32
Variable slope
rate
) are equal, speed reference (
23.02 Speed ref ramp
output
) is a straight line.
This function is only active in remote control.
Off
Off
Variable slope disabled.
0
On
Variable slope enabled (not available in local control).
1
23.29
Variable slope rate
Defines the rate of the speed reference change when
variable slope is enabled by parameter
23.28
Variable
slope enable
.
For the best result, enter the reference update interval into
this parameter.
50 ms
2…30000 ms
Variable slope rate.
1 = 1 ms
No.
Name/Value
Description
Default
FbEq 16
t
Speed
reference
23.02
Speed ref ramp output
Speed reference
Time
A
t = update interval of signal from external control system
A = speed reference change during t
ACS380 FW.book Page 192 Friday, May 4, 2018 4:18 PM