164 Parameters
20.22
Enable to rotate
Setting this parameter to 0 stops motor rotating but does
not affect any other conditions for rotating. Setting the
parameter back to 1 starts motor rotating again.
This parameter can be used for example with a signal
from some external equipment to prevent the motor
rotating before the equipment is ready.
When this parameter is 0 (rotating of the motor is
disabled), bit 13 of parameter
06.16
Drive status word 1
is set to 0.
Selected
Not selected
0 (always off).
0
Selected
1 (always on).
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status,
bit 0). 11
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status,
bit 1). 12
Timed function 1
Bit 0 of
34.01Timed functions status
.
18
Timed function 2
Bit 1 of
34.01
Timed functions status
.
19
Timed function 3
Bit 2 of
34.01
Timed functions status
.
20
Supervision 1
Bit 0 of
32.01 Supervision status
.
24
Supervision 2
Bit 1 of
32.01 Supervision status
.
25
Supervision 3
Bit 2 of
32.01 Supervision status
.
26
Supervision 4
Bit 3 of
32.01 Supervision status
.
27
Supervision 5
Bit 4 of
32.01 Supervision status
.
28
Supervision 6
Bit 5 of
32.01 Supervision status
.
29
Other [bit]
Source selection (see
Terms and abbreviations
).
-
20.25
Jog enable
Selects the source for a jog enable signal.
(The sources for jogging activation signals are selected by
parameters
20.26
Jog 1 start
and
20.27
Jog 2 start
.)
1 = Jogging is enabled.
0 = Jogging is disabled.
Notes:
• Jogging is supported in vector control mode only.
• Jogging can be enabled only when no start command
from an external control location is active. On the other
hand, if jogging is already enabled, the drive cannot be
started from an external control location (apart from
inching commands through fieldbus).
See section
Rush control
on page
70
.
Not selected
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 164 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de