Parameters 267
40.35
Set 1 derivation filter
time
Defines the time constant of the 1-pole filter used to
smooth the derivative component of the process PID
controller.
0.0 s
0.0…10.0 s
Filter time constant.
10 = 1 s
40.36
Set 1 output min
Defines the minimum limit for the process PID controller
output. Using the minimum and maximum limits, it is
possible to restrict the operation range.
0.00
-200000.00…
200000.00
Minimum limit for process PID controller output.
1 = 1
40.37
Set 1 output max
Defines the maximum limit for the process PID controller
output. See parameter
40.36
Set 1 output min
.
100.00
-200000.00…
200000.00
Maximum limit for process PID controller output.
1 = 1
40.38
Set 1 output freeze
enable
Freezes (or defines a source that can be used to freeze)
the output of the process PID controller, keeping the
output at the value it was before freeze was enabled. This
feature can be used when, for example, a sensor
providing process feedback must to be serviced without
stopping the process.
1 = Process PID controller output frozen
See also parameter
40.30
Set 1 setpoint freeze enable
.
Not selected
Not selected
Process PID controller output not frozen.
0
Selected
Process PID controller output frozen.
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0). 10
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status
, bit 1) 11
Timed function 1
Bit 0 of
34.01
Timed functions status
.
18
No.
Name/Value
Description
Default
FbEq 16
63
%
100
T
t
O = I × (1 - e
-t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
ACS380 FW.book Page 267 Friday, May 4, 2018 4:18 PM