252 Parameters
36
36 Load analyzer
Peak value and amplitude logger settings.
See also section
Load analyzer
(page
104
).
36.01
PVL signal source
Selects the signal to be monitored by the peak value
logger.
The signal is filtered using the filtering time specified by
parameter
36.02 PVL filter time
.
The peak value is stored, along with other pre-selected
signals at the time, into parameters
36.10
…
36.15
.
The peak value logger can be reset using parameter
36.09 Reset loggers
. The date and time of the last reset
are stored into parameters
36.16
and
36.17
respectively.
Output
power
Not selected
None (peak value logger disabled).
0
Motor speed used
01.01
Motor speed used
.
1
Output frequency
01.06
Output frequency
.
3
Motor current
01.07
Motor current
.
4
Motor torque
01.10
Motor torque
.
6
DC voltage
01.11
DC voltage
.
7
Output power
01.14
Output power
. 8
Speed ref ramp in
23.01
Speed ref ramp input
.
10
Speed ref ramp out
23.02
Speed ref ramp output
.
11
Speed ref used
24.01
Used speed reference
.
12
Torque ref used
26.02
Torque reference used
. 13
Freq ref used
28.02
Frequency ref ramp output
.
14
Process PID out
40.01
Process PID output actual
.
16
Other
Source selection (see
Terms and abbreviations
).
-
36.02
PVL filter time
Peak value logger filtering time. See parameter
36.01
PVL
signal source
.
2.00 s
0.00…120.00 s
Peak value logger filtering time.
100 = 1 s
36.06
AL2 signal source
Selects the signal to be monitored by amplitude logger 2.
The signal is sampled at 200 ms intervals.
The results are displayed by parameters
36.40
…
36.49
.
Each parameter represents an amplitude range, and
shows what portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter
36.07
AL2 signal scaling
.
Amplitude logger 2 can be reset using parameter
36.09
Reset loggers
. The date and time of the last reset are
stored into parameters
36.50
and
36.51
respectively.
For the selections, see parameter
36.01
PVL signal
source
.
Motor torque
See parameter
36.01
for the selections.
36.07
AL2 signal scaling
Defines the monitored signal value for the amplitude
logger AL2 that corresponds to 100% sample value.
100.00
0.00…32767.00
Signal value corresponding to 100%.
1 = 1
36.09
Reset loggers
Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Done
Reset completed or not requested (normal operation).
0
No.
Name/Value
Description
Default
FbEq 16