Parameters 249
35.22
Temperature 2 fault
limit
Defines the fault limit for temperature supervision
function 2. The unit is selected by parameter
96.16
Unit
selection
.
Note:
With a PTC sensor, the unit is ohms.
130 °C
-60…5000 °C
Fault limit for temperature monitoring function 2.
1 = 1 unit
35.23
Temperature 2
warning limit
Defines the warning limit for temperature supervision
function 2. The unit is selected by parameter
96.16
Unit
selection
.
Note:
With a PTC sensor, the unit is ohms.
110 °C
-60…5000 °C
Warning limit for temperature monitoring function 2.
1 = 1 unit
35.24
Temperature 2 AI
source
Selects the input for parameter
35.21
Temperature 2
source
selection
Direct temperature
.
Not selected
Not selected
None.
0
AI1 actual value
Analog input AI1 on the control unit.
1
AI2 actual value
Analog input AI2 on the control unit.
2
Other
Source selection (see
Terms and abbreviations
).
-
35.50
Motor ambient
temperature
Defines the ambient temperature of the motor for the
motor thermal protection model. The unit is selected by
parameter
96.16
Unit selection
.
The motor thermal protection model estimates the motor
temperature on the basis of parameters
35.50
…
35.55
.
The motor temperature increases if it operates in the
region above the load curve, and decreases if it operates
in the region below the load curve.
WARNING!
The model cannot protect the motor if
the motor does not cool properly because of dust,
dirt, etc.
20 °C or
68 °F
-60…100 °C or
-75 … 212 °F
Ambient temperature.
1 = 1°
No.
Name/Value
Description
Default
FbEq 16