332 Parameters
96.04
Macro select
Selects the control macro. See chapter
Control macros
for
more information.
After a selection is made, the parameter reverts
automatically to
Done
.
Note: When you change the default parameter values of a
macro, the new settings become valid immediately and
stay valid even if the power of the drive is switched off and
on. However, backup of the default parameter settings
(factory settings) of each standard macro is still available.
Done
Done
Macro selection complete; normal operation.
0
ABB standard
ABB standard macro
. For scalar motor control.
1
AC500 Modbus RTU
AC500 Modbus RTU
5
Ethernet IP
Ethernet IP
8
Modbus TCP
Modbus TCP
9
Alternate
Alternate macro
12
Motor potentiometer
Motor potentiometer macro
13
PID
PID control macro
14
96.05
Macro active
Shows which control macro is currently selected. See
chapter
Control macros
for more information.
To change the macro, use parameter
96.04
Macro select
.
ABB
standard
Done
Macro selection complete; normal operation.
0
ABB standard
ABB standard macro
. For scalar motor control.
1
AC500 Modbus RTU
AC500 Modbus RTU
5
Ethernet IP
Ethernet IP
8
Modbus TCP
Modbus TCP
9
Alternate
Alternate macro
12
Motor potentiometer
Motor potentiometer macro
13
PID
PID control macro
14
96.06
Parameter restore
Restores the original settings of the control program, ie.
parameter default values.
Note:
This parameter cannot be changed while the drive
is running.
Done
Done
Restoring is completed.
0
Restore defaults
All editable parameter values are restored to default
values, except
• motor data and ID run results
• I/O extension module settings
• end user texts, such as customized warnings and faults
(external faults and changed), and the drive name
• control panel/PC communication settings
• fieldbus adapter settings
• control macro selection and the parameter defaults
implemented by it
• parameter
95.20
HW options word 1
and the
differentiated defaults implemented by it.
• user lock configuration parameters
96.100
…
96.102
.
8
No.
Name/Value
Description
Default
FbEq 16