Parameters 155
Torque
Torque control. The torque reference used is
26.74
Torque
ref ramp out
(output of the torque reference chain).
3
Minimum
Combination of selections
Speed
and
Torque
: the torque
selector compares the speed controller output (
25.01
Torque reference speed control
) and the torque reference
(
26.74
Torque ref ramp out
) and selects the smaller of the
two.
If speed error becomes negative, the drive follows the
speed controller output until speed error becomes positive
again. This prevents the drive from accelerating
uncontrollably if the load is lost in torque control.
4
Maximum
Combination of selections
Speed
and
Torque
: the torque
selector compares the speed controller output (
25.01
Torque reference speed control
) and the torque reference
(
26.74
Torque ref ramp out
) and selects the greater of the
two.
If speed error becomes positive, the drive follows the
speed controller output until speed error becomes
negative again. This prevents the drive from accelerating
uncontrollably if the load is lost in torque control.
5
19.14
Ext2 control mode
Selects the operating mode for external control location
EXT2 in vector motor control mode.
For the selections, see parameter
19.12
Ext1 control
mode
.
Speed
19.16
Local control mode
Selects the operating mode for local control in vector
motor control mode.
Speed
Speed
Speed control. The torque reference used is
25.01
Torque
reference speed control
(output of the speed reference
chain).
0
Torque
Torque control. The torque reference used is
26.74
Torque
ref ramp out
(output of the torque reference chain).
1
19.17
Local control disable
Enables/disables local control (start and stop buttons on
the control panel, and the local controls on the PC tool).
WARNING!
Before disabling local control, ensure
that the control panel is not needed for stopping
the drive.
No
No
Local control enabled.
0
Yes
Local control disabled.
1
20
20 Start/stop/direction
Start/stop/direction and run/start/jog enable signal source
selection; positive/negative reference enable signal
source selection.
For information on control locations, see section
Local
and external control locations
(page
52
).
20.01
Ext1 commands
Selects the source of start, stop and direction commands
for external control location 1 (EXT1).
See also parameters
20.02
…
20.05
. See parameter
20.21
for the determination of the actual direction.
In1 Start; In2
Dir
Not selected
No start or stop command sources selected.
0
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 155 Friday, May 4, 2018 4:18 PM