Parameters 237
32.45
Supervision 5 function
Selects the mode of signal supervision function 5.
Determines how the monitored signal (see parameter
32.47
) is compared to its lower and upper limits (
32.49
and
32.40
respectively). The action to be taken when the
condition is fulfilled is selected by
32.46
.
Disabled
Disabled
Signal supervision 5 not in use.
0
Low
Action is taken whenever the signal falls below its lower
limit.
1
High
Action is taken whenever the signal rises above its upper
limit.
2
Abs low
Action is taken whenever the absolute value of the signal
falls below its (absolute) lower limit.
3
Abs high
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both
Action is taken whenever the signal falls below its low limit
or rises above its high limit.
5
Abs both
Action is taken whenever the absolute value of the signal
falls below its (absolute) low limit or rises above its
(absolute) high limit.
6
Hysteresis
Action is taken whenever the signal rises above the value
defined by the limit + 0.5 · hysteresis range (
32.51
Supervision 5 hysteresis
). The action is deactivated when
the signal falls below the value defined by the limit - 0.5 ·
hysteresis range.
7
32.46
Supervision 5 action
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 5
exceeds its limits.
Note:
This parameter does not affect the status indicated
by
32.01
Supervision status
.
No action
No action
No warning or fault generated.
0
Warning
Warning
A8B0
Signal supervision
is generated.
1
Fault
The drive trips on fault
80B0
Signal supervision
.
2
Fault if running
The drive trips on fault
80B0
Signal supervision
if running. 3
32.47
Supervision 5 signal
Selects the signal to be monitored by signal supervision
function 5.
For the available selections, see parameter
32.07
Supervision 1 signal
.
Zero
32.48
Supervision 5 filter
time
Defines a filter time constant for the signal monitored by
signal supervision 5.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
32.49
Supervision 5 low
Defines the lower limit for signal supervision 5.
0.00
-21474830.00…
21474830.00
Low limit.
-
32.50
Supervision 5 high
Defines the upper limit for signal supervision 5.
0.00
-21474830.00…
21474830.00
Upper limit.
-
32.51
Supervision 5
hysteresis
Defines the hysteresis for the signal monitored by signal
supervision 5.
0.00
0.00…100000.00
Hysteresis.
-
No.
Name/Value
Description
Default
FbEq 16