![ABB ACS380 Series Скачать руководство пользователя страница 468](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560468.webp)
468 Fieldbus control through the embedded fieldbus interface (EFB)
1017h 0
Producer
Heartbeat
Time
U16
RW
The producer heartbeat time defines the
cycle time of the heartbeat. If the time is 0
it is not used. The time has to be a
multiple of 1 ms.
1018h 0
Number of
Entries
U8
RO
This object contains general information
about the device.
Sub-Index 1 contains the vendor ID (B7h
= ABB)
Sub-Index 2 identifies the drive type.
Sub-Index 3 contains the revision number.
Bit 31-16 is the major revision number and
Bit 15-0 the minor revision number.
Sub-Index 4 contains a numerical
representation of the drive’s serial
number.
1
Vendor ID
U32
RO
2
Product Code U32
RO
3
Module
revision
U32
RO
4
Serial number U32
RO
1400h 0
Number Of
Entries
U8
RO
Contain the communication parameters of
the PDOs the device is able to receive.
Sub-index 0 contains the number of PDO-
parameters implemented.
Sub-index 1 describes the COB-ID for the
PDO. If bit 31 is set the PDO is disabled.
Sub-index 2 defines the transmission
mode.
Sub-index 3 is not used with RPDOs.
Sub-index 5 defines a timeout for
asynchronous PDOs.
1
COB-ID
U32
RW
2
Transmission
Type
U8
RW
3
Inhibit Time
U6
RW
5
Event Timer
U6
RW
1405h 0
Number Of
Entries
U8
RO
1
COB-ID
U32
RW
2
Transmission
Type
U8
RW
3
Inhibit Time
U6
RW
5
Event Timer
U6
RW
1414h 0
Number Of
Entries
U8
RO
1
COB-ID
U32
RW
2
Transmission
Type
U8
RW
3
Inhibit Time
U6
RW
5
Event Timer
U6
RW
Index
Sub-
index
Name
Type
Access Description
ACS380 FW.book Page 468 Friday, May 4, 2018 4:18 PM