122 Parameters
05.83
Motor current at fault
Displays the motor current (
01.07
) at which fault occurred. -
0.00…30000.00 A
Motor current at fault.
See par.
46.05
05.84
Motor torque at fault
Displays the motor torque (
01.10
) at which fault occurred
-
-1600.0…1600.0%
Motor torque at fault.
See par.
46.03
05.85
Main status word at
fault
Displays the main status word (
06.11
) at which fault
occurred. For the bit list, see parameter
06.11
Main status
word
.
0000h
0000h…FFFFh
Main status word at fault.
1 = 1
05.86
DI delayed status at
fault
Displays the DI delayed status (
10.02
) at which fault
occurred. For the bit list, see parameter
10.02
DI delayed
status
.
0000h
0000h…FFFFh
DI delayed status at fault.
1 = 1
05.87
Inverter temperature
at fault
Displays the inverter temperature (
05.11
) at which fault
occurred.
-
-40…160°C
Inverter temperature at fault.
1 = 1°C
05.88
Reference used at
fault
Displays the reference used (
28.01
/
26.73
/
23.01
) at which
fault occurred. The type of the reference depends on the
selected operation mode (
19.01
).
-
-500.00...500.00 Hz/
-1600.0…1600.0%/
30000.00...
30000.00 rpm
Reference used at fault.
See par.
46.02
/
See par.
46.03
/
See par.
46.01
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
0
Ready to switch ON
1
Ready run
2
Ready ref
3
Tripped
4
Not in use
5
Not in use
6
Not in use
7
Warning
8
Modulating
9
Remote
10
Net OK
11
User bit 0
12
User bit 1
13
User bit 2
14
Charging
15
User bit 3
ACS380 FW.book Page 122 Friday, May 4, 2018 4:18 PM