Parameters 117
01.30
Nominal torque scale
Nominal torque in N•m which corresponds to 100%.
Note: This parameter is copied from parameter
99.12
Motor nominal torque
if given. Otherwise the
value is calculated from other motor data.
0
0.000…4000000
N·m or lb·ft
Nominal torque.
1 = 100 unit
01.50
Current hour kWh
Current hour energy consumption. This is the energy of
the last 60 minutes (not necessarily continuous) the drive
has been running, not the energy of a calendar hour. The
value is set to the value before the power cycle when the
drive is again up and running.
- / -
0.00…1000000.00
kWh
Energy.
1 = 1 kWh
01.51
Previous hour kWh
Previous hour energy consumption. The value
Current
hour kWh
is stored here when its values has been
cumulated for 60 minutes. The value is set to the value
before the power cycle when the drive is again up and
running.
-
0.00…1000000.00
kWh
Energy.
1 = 1 kWh
01.52
Current day kWh
Current day energy consumption. This is the energy of the
last 24 hours (not necessarily continuous) the drive has
been running, not the energy of a calendar day. The value
is set to the value before the power cycle when the drive is
again up and running.
-
0.00…1000000.00
kWh
Energy.
1 = 1 kWh
01.53
Previous day kWh
Previous day energy consumption. The value is set to the
value before the power cycle when the drive is again up
and running.
-
0.00 … 1000000.00
kWh
Energy.
1 = 1 kWh
01.54
Cumulative inverter
energy
Amount of energy that has passed through the drive (in
either direction) in full kilowatt-hours. The minimum value
is zero.
-
-200000000.0…
200000000.0 kWh
Energy in kWh.
10 = 1 kWh
01.55
Inverter GWh counter
(resettable)
Amount of energy that has passed through the drive (in
either direction) in full gigawatt-hours. The minimum value
is zero.
You can reset the value by setting it to zero. Resetting any
of parameters
01.55
…
01.58
resets all of them.
-
0…65535 GWh
Energy in GWh.
1 = 1 GWh
01.56
Inverter MWh counter
(resettable)
Amount of energy that has passed through the drive (in
either direction) in full megawatt-hours. Whenever the
counter rolls over,
01.55
Inverter GWh counter
(resettable)
is incremented. The minimum value is zero.
You can reset the value by setting it to zero. Resetting any
of parameters
01.55
…
01.58
resets all of them.
-
0…1000 MWh
Energy in MWh.
1 = 1 MWh
No.
Name/Value
Description
Default
FbEq 16