150 Parameters
15.05
RO force selection
The electrical statuses of the relay outputs can be
overridden for e.g. testing purposes. A bit in parameter
15.06
RO forced data
is provided for each relay output,
and its value is applied whenever the corresponding bit in
this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
15.05
and
15.06
).
0000h
0000h…FFFFh
Override selection for relay outputs.
1 = 1
15.06
RO forced data
Allows the data value of a forced relay or relay output to
be changed from 0 to 1. It is only possible to force an
output that has been selected in parameter
15.05
RO
force selection
Bits 0…3 are the forced values for RO2…RO5.
0000h
0000h…FFFFh
Forced values of relay outputs.
1 = 1
15.07
RO2 source
Selects a drive signal to be connected to relay output
RO2.
Not
energized
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
Bit 1 of
06.11
Main status word
2
Enabled
Bit 0 of
06.16
Drive status word 1
.
4
Started
Bit 5 of
06.16
Drive status word 1
.
5
Magnetized
Bit 1 of
06.17
Drive status word 2
.
6
Running
Bit 6 of
06.16
Drive status word 1
.
7
Ready ref
Bit 2 of
06.11
Main status word
.
8
At setpoint
Bit 8 of
06.11
Main status word
.
9
Reverse
Bit 2 of
06.19 Speed control status word
.
10
Zero speed
Bit 0 of
06.19 Speed control status word
.
11
Above limit
Bit 10 of
06.17
Drive status word 2
.
12
Warning
Bit 7 of
06.11
Main status word
.
13
Fault
Bit 3 of
06.11
Main status word
.
14
Fault (-1)
Inverted bit 3 of
06.11
Main status word
.
15
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1= Force RO2 to value of bit 0 of parameter
15.06
RO forced data
.
1
1= Force RO3 to value of bit 1 of parameter
15.06
RO forced data
.
2
1= Force RO4 to value of bit 2 of parameter
15.06
RO forced data
.
3
1= Force RO5 to value of bit 3 of parameter
15.06
RO forced data
.
4…15
Reserved
Bit
Value
0
1= Force RO2 to value of bit 0 of parameter
15.05
RO force selection
1
1= Force RO3 to value of bit 1 of parameter
15.05
RO force selection
2
1=Force RO4 to value of bit 2 of parameter
15.05
RO force selection
3
1= Force RO5 to value of bit 3 of parameter
15.05
RO force selection
4...15
Reserved
ACS380 FW.book Page 150 Friday, May 4, 2018 4:18 PM