![ABB ACS380 Series Скачать руководство пользователя страница 309](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560309.webp)
Parameters 309
58.29
EFB act2 type
Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through the embedded
fieldbus interface.
Note:
If parameter
58.01
= [3] CANopen, default value is
set as
Speed or frequency
.
Transparent
Speed or frequency
Type/source and scaling are chosen automatically
according to the currently active operation mode as
follows:
0
Transparent
The value selected by parameter
58.32
EFB act2
transparent source
is sent as actual value 2. No scaling is
applied (the 16-bit scaling is 1 = 1 unit).
1
General
The value selected by parameter
58.32
EFB act2
transparent source
is sent as actual value 2 with a 16-bit
scaling of 100 =1 unit (i.e. integer and two decimals).
2
Torque
01.10
Motor torque
is sent as actual value 2. Scaling is
defined by parameter
46.03
Torque scalingg
.
3
Speed
01.01
Motor speed used
is sent as actual value 2. Scaling
is defined by parameter
46.01
Speed scaling
.
4
Frequency
01.06
Output frequency
is sent as actual value 2. Scaling
is defined by parameter
46.02
Frequency scaling
.
5
58.31
EFB act1 transparent
source
Selects the source of actual value 1 when parameter
58.28
EFB act1 type
is set to
Transparent
.
Not selected
Not selected
None.
0
Other
Source selection (see
Terms and abbreviations
).
-
58.32
EFB act2 transparent
source
Selects the source of actual value 1 when parameter
58.29
EFB act2 type
is set to
Transparent
.
Not selected
Not selected
None.
0
Other
Source selection (see
Terms and abbreviations
).
-
No.
Name/Value
Description
Default
FbEq 16
Operation mode
(see par.
19.01
)
Actual 1 type (source)
Scaling
Speed control
Speed
(
01.01
Motor speed used
)
46.01
Speed scaling
Torque control
Frequency control
Frequency
(
01.06
Output frequency
)
46.02
Frequency scaling
ACS380 FW.book Page 309 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de