144 Parameters
12.19
AI1 scaled at AI1 min
Defines the real internal value that corresponds to the
minimum analog input AI1 value defined by parameter
12.17
AI1 min
. (Changing the polarity settings of
12.19
and
12.20
can effectively invert the analog input.)
0
-32768.000…
32767.000
1 = 1
12.20
AI1 scaled at AI1 max
Defines the real internal value that corresponds to the
maximum analog input AI1 value defined by parameter
12.18
AI1 max
. See the drawing at parameter
12.19
AI1
scaled at AI1 min
.
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI1 value.
1 = 1
12.21
AI2 actual value
Displays the value of analog input AI2 in mA or V
(depending on whether the input is set to current or
voltage by a hardware setting).
This parameter is read-only.
-
0.000…20.000 mA
or 0.000…10.000 V
Value of analog input AI2.
1000 = 1 mA
or V
12.22
AI2 scaled value
Displays the value of analog input AI2 after scaling. See
parameters
12.29
AI2 scaled at AI2 min
and
12.101
AI1
percent value
.
This parameter is read-only.
-
-32768.000…
32767.000
Scaled value of analog input AI2.
1 = 1
12.23
AI2 forced value
Forced value that can be used instead of the true reading
of the input. See parameter
12.02
AI force selectionn
.
-
0.000…20.000 mA
or 0.000…10.000 V
Forced value of analog input AI2.
1000 = 1 mA
or V
12.25
AI2 unit selection
Selects the unit for readings and settings related to analog
input AI2. See the default control connections of the
macro in use, in chapter
Control macros
(page
31
).
mA
V
Volts.
2
mA
Milliamperes.
1
No.
Name/Value
Description
Default
FbEq 16
12.20
12.18
12.17
12.19
AI
in
(
12.11
)
AI
scaled
(
12.12
)
ACS380 FW.book Page 144 Friday, May 4, 2018 4:18 PM