154 Parameters
Min
The torque selector is comparing the output of the speed
controller (
25.01
) and torque reference (
26.74
) and the
smaller of the two is used (in vector motor control mode).
4
Max
The torque selector is comparing the output of the speed
controller (
25.01
) and torque reference (
26.74
) and the
greater of the two is used (in vector motor control mode).
5
Scalar (Hz)
Frequency control in scalar motor control mode (in scalar
motor control mode).
10
Forced magn.
Motor is in magnetizing mode.
20
19.11
Ext1/Ext2 selection
Selects the source for external control location
EXT1/EXT2 selection.
0 = EXT1
1 = EXT2
EXT1
EXT1
EXT1 (permanently selected).
0
EXT2
EXT2 (permanently selected).
1
FBA A MCW bit 11
Control word bit 11 received through fieldbus interface A.
2
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
3
DI2
Digital input DI2 (
10.02 DI delayed status
, bit 1).
4
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
5
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
6
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0) 11
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status
, bit 1) 12
Timed function 1
Bit 0 of
34.01
Timed functions status
.
19
Timed function 2
Bit 1 of
34.01
Timed functions status
.
20
Timed function 3
Bit 2 of
34.01
Timed functions status
.
21
Supervision 1
Bit 0 of
32.01 Supervision status
.
25
Supervision 2
Bit 1 of
32.01
Supervision status
.
26
Supervision 3
Bit 2 of
32.01
Supervision status
.
27
Supervision 4
Bit 3 of
32.01
Supervision status
.
28
Supervision 5
Bit 4 of
32.01
Supervision status
.
29
Supervision 6
Bit 5 of
32.01
Supervision status
.
30
EFB MCW bit 11
Control word bit 11 received through the embedded
fieldbus interface.
32
FBA A connection loss Detected communication loss of fieldbus interface A
changes control mode to EXT2.
33
EFB connection loss
Detected communication loss of embedded fieldbus
interface changes control mode to EXT2.
35
Other [bit]
Source selection (see
Terms and abbreviations
).
-
19.12
Ext1 control mode
Selects the operating mode for external control location
EXT1 in vector motor control mode.
Speed
Zero
None.
1
Speed
Speed control. The torque reference used is
25.01
Torque
reference speed control
(output of the speed reference
chain).
2
No.
Name/Value
Description
Default
FbEq 16