246 Parameters
35.11
Temperature 1 source
Selects the source from which measured temperature 1 is
read.
Usually this source is from a sensor connected to the
motor controlled by the drive, but it could be used to
measure and monitor a temperature from other parts of
the process as long as a suitable sensor is used as per
the selection list.
Estimated
temperature
Disabled
None. Temperature monitoring function 1 is disabled.
0
Estimated temperature Estimated motor temperature (see parameter
35.01
Motor
estimated temperature
).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient
temperature of the motor in
35.50
Motor ambient
temperature
.
1
KTY84 analog I/O
KTY84 sensor connected to the analog input selected by
parameter
35.14
Temperature 1 AI source
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
12 Standard AI
to
V
(volt).
• In parameter group
13 Standard AO
, set the source
selection parameter of the analog output to
Temp
sensor 1 excitation
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along
with its temperature, the voltage over the sensor
increases. The voltage is read by the analog input and
converted into degrees.
2
1 x Pt100 analog I/O
Pt100 sensor connected to a standard analog input
selected by parameter
35.14
Temperature 1 AI source
and an analog output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
12 Standard AI
to
V
(volt).
• In parameter group
13 Standard AO
, set the source
selection parameter of the analog output to
Temp
sensor 1 excitation
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along
with its temperature, the voltage over the sensor
increases. The voltage is read by the analog input and
converted into degrees.
5
2 x Pt100 analog I/O
As selection
1 x Pt100 analog I/O
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
6
3 x Pt100 analog I/O
As selection
1 x Pt100 analog I/O
, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
7
No.
Name/Value
Description
Default
FbEq 16