![ABB ACS380 Series Скачать руководство пользователя страница 156](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560156.webp)
156 Parameters
In1 Start
The source of the start and stop commands is selected by
parameter
20.03
Ext1 in1 source
. The state transitions of
the source bits are interpreted as follows:
1
In1 Start; In2 Dir
The source selected by
20.03
Ext1 in1 source
is the start
signal; the source selected by
20.04
Ext1 in2 source
determines the direction. The state transitions of the
source bits are interpreted as follows:
2
In1 Start fwd; In2 Start
rev
The source selected by
20.03
Ext1 in1 source
is the
forward start signal; the source selected by
20.04
Ext1 in2
source
is the reverse start signal. The state transitions of
the source bits are interpreted as follows:
3
In1P Start; In2 Stop
The sources of the start and stop commands are selected
by parameters
20.03
Ext1 in1 source
and
20.04
Ext1 in2
source
. The state transitions of the source bits are
interpreted as follows:
Notes:
• Parameter
20.02
Ext1 start trigger type
has no effect
with this setting.
• When source 2 is 0, the Start and Stop keys on the
control panel are disabled.
4
No.
Name/Value
Description
Default
FbEq 16
State of source 1
(
20.03
)
Command
0 -> 1 (
20.02
=
Edge
)
1 (
20.02
=
Level
)
Start
0
Stop
State of source 1
(
20.03
)
State of source 2
(
20.04
)
Command
0
Any
Stop
0 -> 1 (
20.02
=
Edge
)
1 (
20.02
=
Level
)
0
Start forward
1
Start reverse
State of source 1
(
20.03
)
State of source 2
(
20.04
)
Command
0
0
Stop
0 -> 1 (
20.02
=
Edge
)
1 (
20.02
=
Level
)
0
Start forward
0
0 -> 1 (
20.02
=
Edge
)
1 (
20.02
=
Level
)
Start reverse
1
1
Stop
State of source 1
(
20.03
)
State of source 2
(
20.04
)
Command
0 -> 1
1
Start
Any
0
Stop
ACS380 FW.book Page 156 Friday, May 4, 2018 4:18 PM