Program features 71
When jogging is activated, the drive starts and accelerates to the defined jogging
speed along the defined jogging acceleration ramp. After the activation signal
switches off, the drive decelerates to a stop along the defined jogging deceleration
ramp.
The figure and table below provide an example of how the drive operates during
jogging. In the example, the ramp stop mode is used (
21.03
Stop mode
).
Jog cmd = State of source set by
20.26
or
20.27
Jog enable = State of source set by
20.25
Start cmd = State of drive start command.
Phase
Jog
cmd
Jog
enable
Start
cmd
Description
1-2
1
1
0
Drive accelerates to the jogging speed along the acceleration
ramp of the jogging function.
2-3
1
1
0
Drive follows the jog reference.
3-4
0
1
0
Drive decelerates to zero speed along the deceleration ramp
of the jogging function.
4-5
0
1
0
Drive is stopped.
5-6
1
1
0
Drive accelerates to the jogging speed along the acceleration
ramp of the jogging function.
6-7
1
1
0
Drive follows the jog reference.
7-8
0
1
0
Drive decelerates to zero speed along the deceleration ramp
of the jogging function.
8-9
0
1->0
0
Drive is stopped. As long as the jog enable signal is on, start
commands are ignored. After jog enable switches off, a fresh
start command is required.
9-10
x
0
1
Drive accelerates to the speed reference along the selected
acceleration ramp (parameters
23.11
…
23.15
).
2 3
1
4 5 6
8
11
13
14 15 16
t
7
18
9
12
10
17
Jog cmd
Jog enable
Start cmd
Speed
ACS380 FW.book Page 71 Friday, May 4, 2018 4:18 PM