![ABB ACS380 Series Скачать руководство пользователя страница 158](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560158.webp)
158 Parameters
20.03
Ext1 in1 source
Selects source 1 for parameter
20.01
Ext1 commands
.
DI1
Always off
0 (always off).
0
Always on
1 (always on).
1
DI1
Digital input DI1 (
10.02 DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02 DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02 DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0). 10
DIO2
Digital input/output (
11.02
DIO delayed status
, bit 1).
11
Timed function 1
Bit 0 of
34.01
Timed functions status
.
18
Timed function 2
Bit 1 of
34.01
Timed functions status
.
19
Timed function 3
Bit 2 of
34.01
Timed functions status
.
20
Supervision 1
Bit 0 of
32.01
Supervision status
.
24
Supervision 2
Bit 1 of
32.01
Supervision status
.
25
Supervision 3
Bit 2 of
32.01
Supervision status
.
26
Supervision 4
Bit 3 of
32.01
Supervision status
.
27
Supervision 5
Bit 4 of
32.01
Supervision status
.
28
Supervision 6
Bit 5 of
32.01
Supervision status
.
29
Other [bit]
Source selection (see
Terms and abbreviations
).
-
20.04
Ext1 in2 source
Selects source 2 for parameter
20.01
Ext1 commands
.
For the available selections, see parameter
20.03
Ext1
in1 source
.
DI2
20.05
Ext1 in3 source
Selects source 3 for parameter
20.01
Ext1 commands
.
For the available selections, see parameter
20.03
Ext1
in1 source
.
Always off
20.06
Ext2 commands
Selects the source of start, stop and direction commands
for external control location 2 (EXT2).
See also parameters
20.07
…
20.10
. See parameter
20.21
for the determination of the actual direction.
Not selected
Not selected
No start or stop command sources selected.
0
In1 Start
The source of the start and stop commands is selected by
parameter
20.08
Ext2 in1 source
. The state transitions of
the source bits are interpreted as follows:
1
No.
Name/Value
Description
Default
FbEq 16
State of source 1
(
20.08
)
Command
0 -> 1 (
20.07
=
Edge
)
1 (
20.07
=
Level
)
Start
0
Stop
ACS380 FW.book Page 158 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |