Program features 105
For amplitude logger 2, the user can select a signal to be sampled at 200 ms
intervals, and specify a value that corresponds to 100%. The collected samples are
sorted into 10 read-only parameters according to their amplitude.
•
Parameter 1 shows the share of samples that have fallen in range 0... 10% of
the reference value during the time that the logging has been active.
•
Parameter 2 shows that share of samples that have fallen in range 10...20% of
the reference value during the time that the logging has been active
•
etc.
You can view this graphically with the assistant panel or the Drive composer PC tool.
Amplitude logger 1 is fixed to monitor motor current, and cannot be reset. With
amplitude logger 1, 100% corresponds to the maximum output current of the drive
(
I
max
). The maximum output current values are listed in the section
Ratings
in the
Hardware manual
of the drive. The measured current is logged continuously. The
distribution of samples is shown by parameters
36.20
…
36.29
.
Settings
Parameter group
36 Load analyzer
(page
252
).
sh
ar
e o
f a
ll sam
p
le
s
0…
10
%
10
…
20%
20
…
30%
30
…
40%
40
…
50%
50
…
60%
60
…
70%
70
…
80%
80
…
90%
>9
0%
Amplitude ranges
(parameters
36.40
…
36.49
)
ACS380 FW.book Page 105 Friday, May 4, 2018 4:18 PM