![ABB ACS380 Series Скачать руководство пользователя страница 281](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560281.webp)
Parameters 281
44.12
Brake close request
Selects the source of an external brake close request
signal. When on, the signal overrides the internal logic
and closes the brake.
0 = Normal operation/No external close signal connected
1 = Close brake
Notes:
• In an open-loop (encoderless) application, if the brake
is kept closed by a brake close request against a
modulating drive for longer than 5 seconds, the brake is
forced to close and the drive trips on a fault,
71A5
Mechanical brake opening not allowed
• This parameter cannot be changed while the drive is
running.
Not selected
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0). 10
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status
, bit 1) 11
Timed function 1
Bit 0 of
34.01 Timed functions status
.
18
Timed function 2
Bit 1 of
34.01 Timed functions status
.
19
Timed function 3
Bit 2 of
34.01 Timed functions status
.
20
Supervision 1
Bit 0 of
32.01 Supervision status
24
Supervision 2
Bit 1 of
32.01 Supervision status
25
Supervision 3
Bit 2 of
32.01 Supervision status
.
26
Supervision 4
Bit 3 of
32.01 Supervision status
.
27
Supervision 5
Bit 4 of
32.01 Supervision status
.
28
Supervision 6
Bit 5 of
32.01 Supervision status
.
29
Other [bit]
Source selection (see
Terms and abbreviations
).
-
44.13
Brake close delay
Specifies a delay between a close command (that is,
when the brake control output is de-energized) and when
the drive stops modulating. This is to keep the motor live
and under control until the brake actually closes.
Set this parameter equal to the value specified by the
brake manufacturer as the mechanical make-up time of
the brake.
0.00 s
0.00…60.00 s
Brake close delay.
100 = 1 s
44.14
Brake close level
Defines the brake close speed as an absolute value.
After motor speed has decelerated to this level, a close
command is given.
10.00 rpm
0.00…1000.00 rpm
Brake close speed.
See par.
46.01
44.15
Brake close level
delay
Defines a brake close level delay. See parameter
44.14
Brake close level
.
0.00 s
0.00 … 10.00 s
Brake close level delay.
100 = 1 s
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 281 Friday, May 4, 2018 4:18 PM