320 Parameters
58.122 RPDO21 word 2
Selects a parameter that is mapped to RPDO21 word 2.
For selections, see parameter
58.101
TPDO1 word 1
.
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
None
58.123 RPDO21 word 3
Selects a parameter that is mapped to RPDO21 word 3.
For selections, see parameter
58.101
TPDO1 word 1
.
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
None
58.124 RPDO21 word 4
Selects a parameter that is mapped to RPDO21 word 4.
For selections, see parameter
58.101
TPDO1 word 1
.
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
None
71
71 External PID1
Configuration of external PID.
71.01
External PID act value
See parameter
40.01
Process PID output actual
.
-
71.02
Feedback act value
See parameter
40.02
Process PID feedback actual
.
-
71.03
Setpoint act value
See parameter
40.03
Process PID setpoint actual
.
-
71.04
Deviation act value
See parameter
40.04
Process PID deviation actual
.
-
71.06
PID status word
Displays status information on process external PID
control.
This parameter is read-only.
-
0000h…FFFFh
Process PID control status word.
1 = 1
71.07
PID operation mode
See parameter
40.07
Process PID operation mode
.
Off
71.08
Feedback 1 source
See parameter
40.08
Set 1 feedback 1 source
.
Not selected
71.11
Feedback filter time
See parameter
40.11
Set 1 feedback filter time
.
0.000 s
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Value
0
PID active
1 = Process PID control active.
1
Reserved
2
Output frozen
1 = Process PID controller output frozen. Bit is set if parameter
71.38
Output freeze enable
is TRUE, or the deadband function is
active (bit 9 is set).
3…6
Reserved
7
Output limit high
1 = PID output is being limited by par.
40.37
.
8
Output limit low
1 = PID output is being limited by par.
40.36
.
9
Deadband active
1 = Deadband is active.
10…11 Reserved
12
Internal setpoint
active
1 = Internal setpoint active (see par.
40.16
…
40.16
)
13…15 Reserved
ACS380 FW.book Page 320 Friday, May 4, 2018 4:18 PM