316 Parameters
58.91
RPDO21 COB-ID
Set the COB-ID of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after the
control unit is rebooted or the new settings validated by
parameter
58.06
Communication control
(
Refresh
settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
0x0000
0x0000...0x07ff
COB-ID.
0 = RPDO disabled,
1 = use COB-ID from CiA 301 pre-defined connection set,
<other value> = use selected COB-ID.
1=1
58.92
TPDO21 transmission
type
Set the transmission type of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after the
control unit is rebooted or the new settings validated by
parameter
58.06
Communication control
(
Refresh
settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
255
0...255
Transmission type.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254…255 = asynchronous
1=1
58.93
TPDO21 event timer
Set the event timer of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after the
control unit is rebooted or the new settings validated by
parameter
58.06
Communication control
(
Refresh
settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
0
0...65535
Event timer
0 = no timeout
other = if this PDO is enabled and has not been
transmitted for event timer milliseconds, a transmission is
forced
1=1 ms
No.
Name/Value
Description
Default
FbEq 16