330 Parameters
External 24V
The drive control board is powered from an external
power supply.
1
95.15
Special HW settings
Contains hardware-related settings that can be enabled
and disabled by toggling the specific bits.
Note
: The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the
drive.
-
0…1
Hardware options configuration word.
1 = 1
95.20
HW options word 1
Specifies hardware-related options that require
differentiated parameter defaults.
This parameter is not affected by a parameter restore.
-
0000h…FFFFh
Hardware options configuration word.
1 = 1
96
96 System
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection; parameter checksum
calculation; user lock.
96.01
Language
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily
supported.
• This parameter does not affect the languages visible in
the Drive composer PC tool. (Those are specified
under
View
–
Settings
–
Drive default language
.)
Not selected
Not selected
Select a language.
0
English
English.
1033
Deutsch
German.
1031
Italiano
Italian.
1040
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Information
0
Reserved
-
1
ABB Sine filter
1 = An ABB sine filter is connected to the output of the drive/inverter
2...15
Reserved
-
Bit
Name
Value
0
Supply frequency
60 Hz
If you change the value of this bit, you have to do a complete reset to
the drive after the change. After reset you have to reselect the macro
to be used.
See section
Differences in the default values between 50 Hz and
60 Hz supply frequency settings
on page
354
. 0 = 50 Hz.
1 = 60 Hz.
1…12
Reserved
13
du/dt filter
activation
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
14…15 Reserved