312 Parameters
58.77
RPDO1 transmission
type
Set the transmission type of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after the
control unit is rebooted or the new settings
validated by parameter
58.06
Communication control
(
Refresh settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
255
0...255
Transmission type.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254…255 = asynchronous
1=1
58.78
RPDO1 event timer
Set the event timer of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after the
control unit is rebooted or the new settings validated by
parameter
58.06
Communication control
(
Refresh
settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
0
0...65535
Defines the time-out time for the PDO.
0 = no timeout
other = if this PDO is enabled and not received for event
timer milliseconds,
58.14
Communication loss time
is
performed.
Note
: The timeout supervision is activated upon a
successful reception of the RPDO.
1=1 ms
58.79
TPDO1 COB-ID
Set the COB-ID of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after the
control unit is rebooted or the new settings validated by
parameter
58.06
Communication control
(
Refresh
settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
0x0001
0x0000...0x07ff
COB-ID.
0 = RPDO disabled, 1 = use COB-ID from CiA 301 pre-
defined connection set, <other value> = use selected
COB-ID.
1=1
58.80
TPDO1 transmission
type
Set the transmission type of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after the
control unit is rebooted or the new settings validated by
parameter
58.06
Communication control
(
Refresh
settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
255
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 312 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de