Parameters 251
35.54
Motor nominal
temperature rise
Defines the temperature rise of the motor above ambient
when the motor is loaded with nominal current. See the
motor manufacturer's recommendations.
The unit is selected by parameter
96.16
Unit selection
.
80 °C or
176 °F
0…300 °C or
32…572 °F
Temperature rise.
1 = 1°
35.55
Motor thermal time
constant
Defines the thermal time constant for use with the motor
thermal protection model, defined as the time to reach
63% of the nominal motor temperature. See the motor
manufacturer's recommendations.
256 s
100…10000 s
Motor thermal time constant.
1 = 1 s
No.
Name/Value
Description
Default
FbEq 16
Motor nominal
temperature rise
Temperature
Time
Ambient temperature
100%
63%
100%
Time
Time
Motor thermal time
Motor current
Temperature rise
ACS380 FW.book Page 251 Friday, May 4, 2018 4:18 PM