406 Fault tracing
6481
Task overload
Internal fault.
Reboot the control unit (using parameter
96.08
Control board boot
) or by cycling
power. If the problem persists, contact
your local ABB representative
6487
Stack overflow
Internal fault.
Reboot the control unit (using parameter
96.08
Control board boot
) or by cycling
power. If the problem persists, contact
your local ABB representative
64A1
Internal file load
File read error.
Reboot the control unit (using parameter
96.08
Control board boot
) or by cycling
power. If the problem persists, contact
your local ABB representative
64A6
Adaptive program file
incompatible or
corrupted
Adaptive program has faulted.
Check the auxiliary code. See actions for
each code below.
000A
Program corrupted or block
non-existent.
Restore the template program or
download the program to the drive.
000C
Required block input missing.
Check the inputs of the block.
000E
Program corrupted or block
non-existent.
Restore the template program or
download the program to the drive.
0011
Program too large.
Remove blocks until the error stops.
0012
Program is empty.
Correct the program and download it to
the drive.
001C
A non-existing parameter or
block is used in the parameter.
Edit the program to correct the parameter
reference, or use an existing block.
001E
Output to parameter failed
because the parameter was
write-protected.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
0023
Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
0024
Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
Other
-
Contact your local ABB representative,
quoting the auxiliary code.
64B2
User set fault
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using parameter
96.08
Control board boot
) or by cycling
power. If the problem persists, contact
your local ABB representative
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
96.07
Parameter save manually
. Retry.
Code
(hex)
Fault / Aux. code
Cause
What to do
ACS380 FW.book Page 406 Friday, May 4, 2018 4:18 PM