![ABB ACS380 Series Скачать руководство пользователя страница 198](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560198.webp)
198 Parameters
25.06
Acc comp derivation
time
Defines the derivation time for acceleration(/deceleration)
compensation. In order to compensate for a high inertia
load during acceleration, a derivative of the reference is
added to the output of the speed controller. The principle
of a derivative action is described under parameter
25.04
Speed derivation time
.
Note:
As a general rule, set this parameter to the value
between 50 and 100% of the sum of the mechanical time
constants of the motor and the driven machine.
The figure below shows the speed responses when a high
inertia load is accelerated along a ramp.
No acceleration compensation:
Acceleration compensation:
0.00 s
0.00…1000.00 s
Acceleration compensation derivation time.
10 = 1 s
25.07
Acc comp filter time
Defines the acceleration (or deceleration) compensation
filter time constant. See parameters
25.04
Speed
derivation time
and
25.06
Acc comp derivation time
.
8.0 ms
0.0…1000.0 ms
Acceleration/deceleration compensation filter time.
1 = 1 ms
25.15
Proportional gain em
stop
Defines the proportional gain for the speed controller
when an emergency stop is active. See parameter
25.02
Speed proportional gain
.
10.00
1.00…250.00
Proportional gain upon an emergency stop.
100 = 1
No.
Name/Value
Description
Default
FbEq 16
Time
Speed reference
Actual speed
Time
Speed reference
Actual speed
ACS380 FW.book Page 198 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |