296 Parameters
50.03
FBA A comm loss t out
Defines the time delay before the action defined by
parameter
50.02
FBA A comm loss func
is taken. Time
count starts when the communication link fails to update
the message.
Note:
There is a 60-second boot-up delay immediately
after power-up. During the delay, the communication
break monitoring is disabled (but communication itself can
be active).
0.3 s
0.3…6553.5 s
Time delay.
1 = 1 s
50.04
FBA A ref1 type
Selects the type and scaling of reference 1 received from
fieldbus adapter A. The scaling of the reference is defined
by parameters
46.01
…
46.04
, depending on which
reference type is selected by this parameter.
Speed or
frequency
Speed or frequency
Type and scaling is chosen automatically according to the
currently active operation mode as follows:
0
Transparent
No scaling is applied.
1
General
Generic reference without a specific unit.
2
Torque
The scaling is defined by parameter
46.03
Torque scaling
. 3
Speed
The scaling is defined by parameter
46.01
Speed scaling
. 4
Frequency
The scaling is defined by parameter
46.02
Frequency
scaling
.
5
50.05
FBA A ref2 type
Selects the type and scaling of reference 2 received from
fieldbus adapter A. The scaling of the reference is defined
by parameters
46.01
…
46.04
, depending on which
reference type is selected by this parameter.
Speed or
frequency
Speed or frequency
Type and scaling is chosen automatically according to the
currently active operation mode as follows:
0
Transparent
No scaling is applied.
1
General
Generic reference without a specific unit.
2
Torque
The scaling is defined by parameter
46.03
Torque scaling
. 3
Speed
The scaling is defined by parameter
46.01
Speed scaling
. 4
Frequency
The scaling is defined by parameter
46.02
Frequency
scaling
.
5
50.06
FBA A SW sel
Selects the source of the status word to be sent to the
fieldbus network through fieldbus adapter A.
Auto
Auto
Source of the status word is chosen automatically.
0
No.
Name/Value
Description
Default
FbEq 16
Operation mode
(see par.
19.01
)
Reference 1 type
Speed control
Speed
Torque control
Speed
Frequency control
Frequency
Operation mode
(see par.
19.01
)
Reference 2 type
Speed control
Torque
Torque control
Torque
Frequency control
Torque
ACS380 FW.book Page 296 Friday, May 4, 2018 4:18 PM