Parameters 233
32.06
Supervision 1 action
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note:
This parameter does not affect the status indicated
by
32.01
Supervision status
.
No action
No action
No warning or fault generated.
0
Warning
Warning
A8B0
Signal supervision
is generated.
1
Fault
The drive trips on fault
80B0
Signal supervision
.
2
Fault if running
The drive trips on fault
80B0
Signal supervision
if running. 3
32.07
Supervision 1 signal
Selects the signal to be monitored by signal supervision
function 1.
Frequency
Zero
None.
0
Speed
01.01
Motor speed used
.
1
Frequency
01.06
Output frequency
.
3
Current
01.07
Motor current
.
4
Torque
01.10 Motor torque
. 6
DC voltage
01.11
DC voltage
.
7
Output power
01.14
Output power
.
8
AI1
12.11
AI1 actual value
.
9
AI2
12.21
AI2 actual value
.
10
Speed ref ramp in
23.01
Speed ref ramp input
.
18
Speed ref ramp out
23.02
Speed ref ramp output
.
19
Speed ref used
24.01
Used speed reference
.
20
Torque ref used
26.02
Torque reference used
.
21
Freq ref used
28.02
Frequency ref ramp output
.
22
Inverter temperature
05.11
Inverter temperature
.
23
Process PID output
40.01
Process PID output actual
.
24
Process PID feedback
40.02
Process PID feedback actual
.
25
Process PID setpoint
40.03
Process PID setpoint actual
.
26
Process PID deviation
40.04
Process PID deviation actual
.
27
Other
Source selection (see
Terms and abbreviations
).
-
32.08
Supervision 1 filter
time
Defines a filter time constant for the signal monitored by
signal supervision 1.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
32.09
Supervision 1 low
Defines the lower limit for signal supervision 1.
0.00
-21474830.00…
21474830.00
Low limit.
-
32.10
Supervision 1 high
Defines the upper limit for signal supervision 1.
0.00
-21474830.00…
21474830.00
Upper limit.
-
32.11
Supervision 1
hysteresis
Defines the hysteresis for the signal monitored by signal
supervision 1.
0.00
0.00…100000.00
Hysteresis.
-
No.
Name/Value
Description
Default
FbEq 16