The recommended setting value of
0.2 I/Irated,S
lies above it.
•
Recommended setting value
(_:105) Slope
=
0.07
You can stabilize the protection function (less sensitive setting) with external multiphase short-circuits to
ground with the parameter
Slope
. To determine the setting value, no pickup value increase can occur up to
the rated current. After this, the gradient must be active. To derive the gradient, it is assumed that continua-
tion of the straight line must go through the coordinate origin (see
). Determine the intersection
from the threshold value and the restraint current at rated current. Calculate the gradient as follows:
[fostbref-231012-01.tif, 1, en_US]
[dwsteiga-221012-01.tif, 2, en_US]
Figure 6-278
Derivation of the Setting Value for the Gradient
If you have several measuring points on an outgoing side (see
), Siemens recommends using the
value 3 I/Irated,S in the intersection calculation for the restraint current. In the load case, the maximum trans-
former rated current flows on one side.
If, however, several measuring points are on the supply side (for example, breaker-and-a-half layout), Siemens
recommends including all phase currents in the intersection calculation, in order to avoid too strong a stabili-
zation. With 2 measuring points, a value of 6 I/Irated,S results as intersection with the threshold value. The
slope becomes flatter (0.2 I/Irated,S/6 I/Irated,S = 0.03).
Protection and Automation Functions
6.43 Restricted Ground-Fault Protection
SIPROTEC 5, Overcurrent Protection, Manual
873
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...