Application and Setting Notes
Parameter:
Level of warning 1
•
Default setting
(_:101) Level of warning 1
=
5 %
With the parameter
Level of warning 1
, you define the percentage the measured value is allowed to
exceed the parameter
CB make time
at the output
Make time
, before the output
Warning 1
is set. The
output
Warning 1
then drops out after 100 ms.
Parameter:
Level of warning 2
•
Default setting
(_:102) Level of warning 2
=
10 %
With the parameter
Level of warning 2
, you define the percentage the measured value is allowed to
exceed the parameter
CB make time
at the output
Make time
, before the output
Warning 2
is set. The
output
Warning 2
then drops out after 100 ms.
Parameter:
Oper.current threshold
•
Default setting
(_:103) Oper.current threshold
=
0.100 A
With the parameter
Oper.current threshold
, you define the current threshold. If the measured value
exceeds this threshold, the measured value is detected as flowing operating current. As soon as an operating
current flows, the end of the time interval
Make time
is detected.
Parameter:
Delay correction time
•
Default setting
(_:104) Delay correction time
=
0.000 s
With the parameter
Delay correction time
, you define a correction value which will be subtracted from
the
Make time
during calculation. This allows you to compensate delays caused by the system, for example,
relay residual times, if necessary.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv.CB mak.t.
_:1
Supv.CB mak.t.:Mode
•
off
•
on
•
test
off
_:101
Supv.CB mak.t.:Level of
warning 1
1 % to 100 %
5 %
_:102
Supv.CB mak.t.:Level of
warning 2
1 % to 100 %
10 %
_:103
Supv.CB
mak.t.:Oper.current
threshold
1 A @ 100 Irated 0.030 A to 35.000 A
0.100 A
5 A @ 100 Irated 0.15 A to 175.00 A
0.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
0.100 A
5 A @ 50 Irated
0.15 A to 175.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:104
Supv.CB mak.t.:Delay
correction time
-0.050 s to 0.050 s
0.000 s
10.12.7.2
10.12.7.3
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring
1368
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...