Binary Output Signal
Description
(_:5161:319) Time
delay different
Signal
Time delay different
indicates that the threshold value for asym-
metrical transit times has been exceeded. The setting value results from the
setting value of the parameter
(_:5161:110) Difference Tx and Rx
time
.
(_:5161:320) Time
delay jump
Signal
Time delay jump
indicates that the data transit times changed
abruptly. This is caused by switching the communication path in the communica-
tion network.
(_:5161:321) PI
synchronized
Signal
PI synchronized
indicates that the protection-interface connection is
synchronized with the opposite end.
(_:5161:340) Tele-
gram lost
Signal
Telegram lost
indicates that an expected telegram has failed to arrive
or a faulty telegram has been received.
If you would like to allocate the communications failures or faults to other events,
move the signal
Telegram lost
temporarily into the operational log. Such
events can be switching operations in the primary system or operations on the
components of the communication network.
Note: If the signal is constantly routed, the operational log can overflow. Siemens
recommends routing the signal only for clarification of faults.
Measured Values of the Protection Interface
The protection interface provides the following measured value to diagnose the protection interface commu-
nication:
Measured Value
Description
(_:5161:308) Tx
tel/h
Telegrams sent during the last hour
(_:5161:309) Rx
tel/h
Telegrams received during the last hour
(_:5161:310) Tx
tel/min
Telegrams sent during the last minute
(_:5161:311) Rx
tel/min
Telegrams received during the last minute
(_:5161:312) Tx
err/h
Transmission failure rate during the last hour
(_:5161:313) Rx
err/h
Receive error rate during the last hour
(_:5161:314) Tx
err/min
Transmission failure rate during the last minute
(_:5161:315) Rx
err/min
Receive error rate during the last minute
(_:5161:325)
Aver.Δt
Mean signal-transit time (average value of the transit time in transmission and
reception direction divided by 2, without GPS synchronization)
(_:5161:326) Rec.
Δt
Signal-transit time in reception direction (with GPS synchronization)
(_:5161:327) Sen.
Δt
Signal-transit time in transmission direction (with GPS synchronization)
(_:5161:334)
Miss.tel/min
Number of telegram failures within the last minute
(_:5161:335)
Miss.tel/h
Number of telegram failures within the last hour
(_:5161:336)
Miss.tel/d
Number of telegram failures within the last day
System Functions
3.5 Protection Communication
SIPROTEC 5, Overcurrent Protection, Manual
137
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...