Directional Intermittent Ground-Fault Protection
Setting Values
Threshold
value 3I0>
For current transformer type
protection and I
rated
= 1 A
0.030 A to 35.000 A
Increments of 0.001 A
For current transformer type
protection and I
rated
= 5 A
0.15 A to 175.00 A
Increments of 0.01 A
For I
N
transformer
type sensitive and
I
N-rated
= 1 A
For I
ph-rated
= 1 A
0.001 A to 35.000 A
Increments of 0.001 A
For I
ph-rated
= 5 A
0.001 A to 175.000 A
Increments of 0.001 A
For I
N
transformer
type sensitive and
I
N-rated
= 5 A
For I
ph-rated
= 1 A
0.005 A to 35.000 A
Increments of 0.001 A
For I
ph-rated
= 5 A
0.005 A to 175.000 A
Increments of 0.001 A
Number of pulses until intermit-
tent ground fault
2 to 10
Increments of 1
Pickup extension time
0.00 s to 10.00 s
Increments of 0.01 s
Sum of extended pickup times
0.00 s to 100.00 s
Increments of 0.01 s
Reset time
1.00 s to 600.00 s
Increments of 0.01 s
Number of pulses for operate
2 to 100
Increments of 1
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer
15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer
0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Times
Pickup time
Approx. 30 ms + OOT
90
at 50 Hz
Approx. 23 ms + OOT at 60 Hz
Dropout time
Approx. 25 ms + OOT at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Active with less sensitivity
12.17
90
OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Technical Data
12.17 Directional Intermittent Ground-Fault Protection
1474
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...