Addr.
Parameter
C
Setting Options
Default Setting
_:4861:8
Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:4861:104
Definite-T 1:Directional
comparison
•
no
•
yes
no
_:4861:106
Definite-T 1:Release via
input signal
•
no
•
yes
no
_:4861:10
Definite-T 1:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:4861:26
Definite-T 1:Dynamic
settings
•
no
•
yes
no
_:4861:27
Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:4861:3
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:4
Definite-T 1:Dropout
ratio
0.90 to 0.99
0.95
_:4861:101
Definite-T 1:Dropout
delay
0.00 s to 60.00 s
0.00 s
_:4861:6
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.s: AR off/n.rdy
_:4861:28
Definite-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:4861:35
Definite-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:4861:29
Definite-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:4861:36
Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:14
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:20
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.set: AR cycle 2
_:4861:30
Definite-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:4861:37
Definite-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground
456
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...