Addr.
Parameter
C
Setting Options
Default Setting
_:691:17
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:691:105
Inverse-T 1:Time dial
0.00 to 15.00
1.00
Dyn.s: Cold load PU
_:691:33
Inverse-T 1:Effect. b.
cold-load pickup
•
no
•
yes
no
_:691:40
Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:691:18
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:691:106
Inverse-T 1:Time dial
0.00 to 15.00
1.00
Dyn.set: bin.input
_:691:34
Inverse-T 1:Effected by
binary input
•
no
•
yes
no
_:691:41
Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:691:19
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:691:107
Inverse-T 1:Time dial
0.00 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Inverse-T 1
_:691:81
Inverse-T 1:>Block stage
SPS
I
_:691:500
Inverse-T 1:>Block delay & op.
SPS
I
_:691:54
Inverse-T 1:Inactive
SPS
O
_:691:52
Inverse-T 1:Behavior
ENS
O
_:691:53
Inverse-T 1:Health
ENS
O
_:691:60
Inverse-T 1:Inrush blocks operate
ACT
O
_:691:59
Inverse-T 1:Disk emulation running
SPS
O
_:691:55
Inverse-T 1:Pickup
ACD
O
_:691:56
Inverse-T 1:Operate delay expired
ACT
O
6.3.5.4
Protection and Automation Functions
6.3 Overcurrent Protection, Phases
348
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...