With the
Threshold light
parameter, you set the light sensitivity. If you set
Threshold light
to a
smaller value, the sensitivity increases. If you set
Threshold light
to a higher value, the sensitivity
decreases. If the sensors even pick up in case of a switching arc of the circuit breaker, set the
Threshold
light
parameter to a higher value.
Siemens recommends the default settings for point or line sensors.
Set the parameter
Threshold light
manually only if you have special default settings for light sensitivity.
Parameter: Channel
•
Default setting
(_:14551:10) Channel
=
No channel is selected
With the
Channel
parameter, you select which sensor channel the stage uses.
If the Arc protection function has several stages, a different channel must be selected for each stage.
For parameter
Channel
, the selection texts are identical to the name of the arc-protection module and its
channels.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:3
General:Threshold I>
1 A @ 100 Irated 0.030 A to 35.000 A
2.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
10.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
2.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
10.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
2.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
10.000 A
_:2311:4
General:Threshold 3I0>
1 A @ 100 Irated 0.030 A to 35.000 A
1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
5.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
5.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
5.000 A
Stage 1
_:14551:1
Stage 1:Mode
•
off
•
on
•
test
off
_:14551:2
Stage 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:14551:9
Stage 1:External trip
initiation
•
no
•
current
•
light
no
_:14551:8
Stage 1:Operating mode
•
light only
•
current and light
current and light
_:14551:11
Stage 1:Sensor
•
point sensor
•
line sensor
•
custom
point sensor
_:14551:7
Stage 1:Threshold light
-34.00 dB to -10.00 dB
-20.00 dB
_:14551:10
Stage 1:Channel
Setting options depend on
configuration
6.10.6
Protection and Automation Functions
6.10 Arc Protection
SIPROTEC 5, Overcurrent Protection, Manual
505
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...