Operate Curve
If the function picks up, the logarithmic inverse-time characteristic curve is processed. A time value T
op
is
calculated for every input value exceeding 95 % of the threshold value. An integrator accumulates the value
1/T
op
. If the accumulated integral reaches the fixed value 1, the stage operates.
The curve used to calculate the time value T
op
is shown in the following graphic. The curve is composed of 2
sections with different slops. 7 parameters are used to define the logarithmic inverse time with knee-point
characteristic curve. The parameter
Max. time of the curve
determines the initial time value of the
characteristic curve, and relates to the 3I0
Threshold
value. The transition point is defined by parameter
Knee-point current
and parameter
Knee-point time
. The parameter
Min. time of the curve
indicates the lower time limit, and parameter
Current at Min. time
determines the current value at
Min. time of the curve
. The parameter
Time dial
servers as a time factor to the operate time.
[dwloinkn-300913, 3, en_US]
Figure 6-77
Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the Example
of
Threshold
=
0.004 A
)
Application and Setting Notes
Apart from the operate curve, this type of stage is almost identical to the Inverse-time overcurrent protec-
tion – advanced stage (see chapter
). The only difference is that the dynamic settings
change functionality is not available.
This section only discusses the nature of the operate curve. For further functionality, refer to chapter
6.7.6.2 Application and Setting Notes
Parameter:
Threshold
•
Default setting
(_:3) Threshold
=
1.20 A
You can use the
Threshold
parameter to define the pickup value of the stage corresponding to the specific
application.
6.7.8.2
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, Overcurrent Protection, Manual
477
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...