_:53
Supv. balan. V:Health
ENS
O
_:71
Supv. balan. V:Failure
SPS
O
Voltage-Sum Supervision
Overview of Functions
In healthy system operation, the sum of all voltages at one measuring point must be approximately 0. The
Voltage-sum supervision monitors the sum of all voltages of one measuring point in the secondary circuit. It
detects connection errors during commissioning or short circuits and interruptions in the secondary circuit. For
summation of the voltages, the 3 phase-to-ground voltages and the residual voltage (da-dn - voltage of an
open-circuited delta winding) are required.
The voltage measurement is based on the RMS values of the fundamental component.
i
i
NOTE
For the Voltage-sum supervision, the externally generated residual voltage must be connected to the 4th
voltage measuring input.
For the Voltage-sum supervision to work correctly, the
Matching ratio Vph / VN
parameter must be
set accordingly.
Structure of the Function
The Voltage-sum supervision function is located in the Power-system data function group of each 3-phase
voltage measuring point.
[dwstrvss-100611-01.tif, 2, en_US]
Figure 9-14
Structure/Embedding of the Function
Function Description
The voltage sum is generated by addition of the voltage phasors. Errors in the voltage circuits are detected if
VF = |VA+ VB + VC + Vph/VN • VN | >
Threshold
, where Vph/VN forms the
Matching ratio Vph / VN
parameter.
9.3.6
9.3.6.1
9.3.6.2
9.3.6.3
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual
1261
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...