Switching to Dead Line/Busbar
If operating modes for switching to dead parts of an electrical power system are configured, the associated
conditions are also checked after the start (see chapter
). The fulfilled conditions are
signaled. An adjustable supervision time is started after the closure conditions are fulfilled (parameter
CB
make time
). If the conditions remain valid until expiry of the time, the function gives the release for closure
after expiry of the time.
Direct Close Command
If the Direct close command operation is active, the function instantaneously initiates the release for closure
after the successful start (see chapter
). A combination of direct close command
with other release conditions is not advisable, as these conditions are bypassed by the direct close command.
End of the Process
If the function is started via the device-internal controller or AREC, these functions also terminate the synchro-
nization process upon closure. The process is terminated via the corresponding binary signals in case of
external starting.
If the supervision time (
Max.durat. sync.process
parameter) has expired, the process is also completed
and the indication
Max. time exceeded
is issued. A renewed synchronization is only possible if the stage is
restarted.
Blocking Closure
You can use the input signal
>Block close command
to block the release signal for the closure (signal
Release close cmd.
) as well as the closure itself. The measurement continues to operate during the
blocking. If the blocking is revoked and the release conditions are still fulfilled, the release is given for closure.
Control Functions
8.4 Synchronization Function
SIPROTEC 5, Overcurrent Protection, Manual
1141
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...