Addr.
Parameter
C
Setting Options
Default Setting
_:6571:110
Cycle 1:Synchroch. aft.
3-pole d.t.
•
none
•
internal
•
external
none
_:6571:112
Cycle 1:Intern. synchro-
check with
Setting options depend on
configuration
Information List
No.
Information
Data Class
(Type)
Type
General
_:6601:51
General:Mode (controllable)
ENC
C
_:6601:87
General:>Function off
SPS
I
_:6601:524
General:>Function on
SPS
I
_:6601:347
General:Function on
SPC
C
_:6601:82
General:>Block function
SPS
I
_:6601:501
General:>Release by ext.sync.
SPS
I
_:6601:502
General:>Blk. with 1-ph pickup
SPS
I
_:6601:503
General:>Blk. with 2-ph pickup
SPS
I
_:6601:504
General:>Blk. with 3-ph pickup
SPS
I
_:6601:505
General:>Blk. 1-pole AR
SPS
I
_:6601:506
General:>Blk. 3-pole AR
SPS
I
_:6601:507
General:>Pickup A for start
SPS
I
_:6601:508
General:>Pickup B for start
SPS
I
_:6601:509
General:>Pickup C for start
SPS
I
_:6601:510
General:>Pickup 1ph for start
SPS
I
_:6601:511
General:>Pickup 2ph for start
SPS
I
_:6601:512
General:>Pickup 3ph for start
SPS
I
_:6601:513
General:>Gen. pickup for start
SPS
I
_:6601:514
General:>General trip for start
SPS
I
_:6601:515
General:>Trip pole A for start
SPS
I
_:6601:516
General:>Trip pole B for start
SPS
I
_:6601:517
General:>Trip pole C for start
SPS
I
_:6601:518
General:>Trip 1-pole for start
SPS
I
_:6601:519
General:>Trip 3-pole for start
SPS
I
_:6601:520
General:>Evolving fault start
SPS
I
_:6601:521
General:>Dead time start delay
SPS
I
_:6601:522
General:>Delay close cmd.
SPS
I
_:6601:52
General:Behavior
ENS
O
_:6601:53
General:Health
ENS
O
_:6601:54
General:Inactive
SPS
O
_:6601:301
General:79 state
ENS
O
_:6601:302
General:Actual reclose cycle
INS
O
_:6601:303
General:Not ready
SPS
O
_:6601:304
General:79 successful
SPS
O
_:6601:305
General:CB ready superv.expir
SPS
O
_:6601:306
General:CB is not ready
SPS
O
_:6601:307
General:79 permits 1-pole trip
SPS
O
6.45.4.20
Protection and Automation Functions
6.45 Automatic Reclosing Function
SIPROTEC 5, Overcurrent Protection, Manual
917
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...