Indication
Type
Group
Warning
Explanation
(_:320)
Auxiliary Power Fail
SPS
Fixed
Fault with the auxiliary power supply:
Check the external power supply.
(_:305)
Battery failure
SPS
Battery fault:
Replace the device battery.
To avoid data losses, Siemens recom-
mends replacing the device battery
when the supply voltage of the device is
switched on.
(_:312)
Compensation error
x
ENS
Calibration error in module x:
Contact the Customer Support Center.
Quality: Measured values are marked
with the quality attribute of
question-
able
(measured value display with ≈).
(_:314)
Offset error
x
ENS
Offset error on module x:
If this indication persists after the device
start, contact the Customer Support
Center.
Quality: Measured values are marked
with the quality attribute of
question-
able
(measured value display with ≈).
(_:306)
Clock fail
SPS
Internal time failure
•
Check the time settings first.
•
Then replace the device battery.
•
If the fault is not remedied, contact
the Customer Support Center.
Quality: The internal time is marked
with the quality attribute of
Clock
Failure
.
(_:319)
Error memory
SPS
Checksum (CRC) error in monitored
memory areas of the device
Measuring-transducer error (x)
ENS
Hardware error on the measuring-trans-
ducer module on plug-in module posi-
tion E/F/M/N/P:
Contact the Customer Support Center.
Handling an alarm:
(_:504)
>Group Warning
SPS
Fixed
Input signal for user-defined generation
of group warning
Time sync.:
(_:305)
Time sync. error
SPS
Fixed
Time synchronization error, the timing
master is faulty:
•
Check the external time source
first.
•
Check the external connections.
•
If the fault is not remedied, contact
the Customer Support Center.
Quality: The internal time is marked
with the quality attribute of
Clock not
synchronized
.
Power-system data:meas. point I-3ph:superv.
bal. I:
(_:71)
Failure
SPS
CFC
Failure of the current balance (see chap.
9.3.10.1 Overview of Functions
)
Supervision Functions
9.8 Error Responses and Corrective Measures
SIPROTEC 5, Overcurrent Protection, Manual
1299
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...