[dwocpken-140611-02.tif, 2, en_US]
Figure 6-40
Pickup Behavior and Dropout Behavior when Using a User-Defined Characteristic Curve
i
i
NOTE
The currents that are lower than the current value of the smallest characteristic-curve point do not extend
the operate time. The pickup characteristic runs in parallel to the current axis up to the smallest character-
istic-curve point. Currents that are larger than the current value of the largest characteristic-curve point do
not reduce the operate time. The pickup characteristic runs in parallel to the current axis from the largest
characteristic-curve point.
If you want to change the pickup threshold of the stage without changing all points of the characteristic curve,
you can use the additional
Threshold (absolute)
parameter.
You can set the
Threshold (absolute)
parameter to be greater than 1.1 times the
Threshold
value.
Then the stage behaviors are as follows:
•
The stage picks up when the measured current value exceeds the
Threshold (absolute)
value.
•
The stage starts dropout when the measured current value falls short of the
Threshold (absolute)
value by 0.95 times.
•
For measured current values lower than the
Threshold (absolute)
value, no pickup takes place and
consequently the characteristic curve is not processed.
If you set the
Threshold (absolute)
parameter to be less than 1.1 times the
Threshold
value, the
pickup and dropout behaviors are not affected by the
Threshold (absolute)
parameter.
Application and Setting Notes
This stage is structured the same way as the Inverse-time overcurrent protection – advanced stage. The
only differences are described in chapter
. This chapter provides only the application and
setting notes for setting characteristic curves and for setting the
Threshold (absolute)
parameter. You
can find more information on the other parameters of the stage in chapter
6.5.5.2 Application and Setting
.
Parameter:
Current/time value pairs
(from the operate curve)
With these settings, you define the characteristic curve. Set a current/time value pair for each characteristic-
curve point. The setting depends on the characteristic curve you want to realize.
6.5.6.2
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
398
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...