Parameter: Tilt power characteristic
•
Recommended setting value
(_:6271:103) Tilt power characteristic
=
+70°
The
Tilt power characteristic
parameter is used to incline the pickup characteristic. In the above
example, an inclination is required. The setting value is
+70°
(for a definition of the sign, see
Parameter: Dropout delay
•
Recommended setting value
(_:6271:7) Dropout delay
=
20 ms
The
Dropout delay
parameter maintains the pickup even if the measured value drops momentarily below
the threshold value. A delay is required for very low pickup values to prevent a so-called chattering of the
function. In the example, the setting value is 20 ms.
Parameter: Operate delay
•
Recommended setting value
(_:6271:6) Operate delay
=
100 ms
The
Operate delay
must be set for the specific application. In the example, a setting value of 100 ms has
been selected.
Setting Notes for the Reactive Power Stage
Stage Type
In the example, the reactive power is to be monitored if it falls below the threshold. In the 3-phase circuit
breaker (P, Q) function, work with the stage type Power Q<.
Parameter: Measured value
•
Recommended setting value
(_:6331:105) Measured value
=
positive seq. power
The
Measured value
parameter is used to specify which measured power value is evaluated. For 3-phase
measurement, Siemens recommends to evaluate the positive-sequence system power.
Parameter: Threshold
•
Recommended setting value
(_:6331:3) Threshold
=
0 %
The
Threshold
parameter is used to define the pickup threshold of the reactive power stage. In the example,
the pickup characteristic runs across the point of origin of the coordinates. Set the parameter
Threshold
to
0
%
.
i
i
NOTE
If you use several settings groups, consider the following:
•
The dropout value of a stage must have the same sign in all settings groups.
•
Switching from a positive dropout value to a negative dropout value or vice versa is not allowed. As a
result, DIGSI reports an inconsistency.
•
If you want to change the sign of the dropout value of a stage in an additional settings group, instan-
tiate a new stage and enable it. If the new stage should not be effective in another settings group,
disable the stage there.
Parameter: Dropout ratio
•
Recommended setting value
(_:6331:101) Dropout ratio
=
0.95
A hysteresis of 5 % is sufficient for most applications. The setting value for the lower stage is therefore 0.95.
6.37.7
Protection and Automation Functions
6.37 Power Protection (P,Q), 3-Phase
SIPROTEC 5, Overcurrent Protection, Manual
805
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...